Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/19/2008

Applicant:

PARK MALL LLC

Description:

Full Inspection conducted 9/18/08

Outstanding Inspections

Case Number: T08FR02976
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
09/19/2008 INSP - FULL DGREENLE Correction Required Certificate of Occupancy NOT ON FILE for current occupant Similar use/hazard level Occupant shall acquire updated C of O
09/19/2008 VIOL - PRECAUTION AGAINST FIRE DGREENLE Violation MISCELLANEOUS COMBUSTIBLE MATERIALS STORAGE TFC 315.2.2 - Means of egress. Combustible materials shall not be stored in exits or exit enclosures. _____ Remove combustable storage from exit hallway.
09/19/2008 VIOL - BUILDING SVCS & SYSTEMS DGREENLE Violation Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panels.
09/19/2008 VIOL - FIRE RESIST.RATED CONST DGREENLE Violation Opening protectives TFC 703.2 - Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable. _____ keep fire doors closed when not in use
09/19/2008 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Violation Portable Fire Extinguishers TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non-required fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ Extinguishers shall be inspected and tagged in accordance with this code, or removed
09/19/2008 VIOL - FIRE PROTECTION SYSTEMS DGREENLE Violation TFC 906.6 - Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. _____ clear obstruction to fire extinguisher - rear of showroom _____ move and re-mount fire extinguisher in an approved manner - stockroom
09/19/2008 VIOL - MEANS OF EGRESS DGREENLE Violation Blocked exit: TFC 1003.6 - Means of egress continuity. Obstructions shall not be placed in the required width of a means of egress....The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear and maintain 28" exit path - stockroom _____ Clear and maintain 36" exit path - showroom to back exit hallway _____ Clear and maintain 36" exit path - back exit hallway
09/19/2008 VIOL - MEANS OF EGRESS DGREENLE Violation MEANS OF EGRESS ILLUMINATION TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Repair or replace emergency lighting units

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02976
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
11/18/2008 INSP - REINSPECTION DGREENLE Approved still trying to get light repaired