Case: T08FR02976
Case Details
Entered Date:
09/19/2008
Applicant:
PARK MALL LLC
Description:
Full Inspection conducted 9/18/08
Outstanding Inspections
Case Number: T08FR02976
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/19/2008 | INSP - FULL | DGREENLE | Correction Required | Certificate of Occupancy NOT ON FILE for current occupant Similar use/hazard level Occupant shall acquire updated C of O |
09/19/2008 | VIOL - PRECAUTION AGAINST FIRE | DGREENLE | Violation | MISCELLANEOUS COMBUSTIBLE MATERIALS STORAGE TFC 315.2.2 - Means of egress. Combustible materials shall not be stored in exits or exit enclosures. _____ Remove combustable storage from exit hallway. |
09/19/2008 | VIOL - BUILDING SVCS & SYSTEMS | DGREENLE | Violation | Blocked electrical panel: TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment. _____ Clear area in front of electrical panels. |
09/19/2008 | VIOL - FIRE RESIST.RATED CONST | DGREENLE | Violation | Opening protectives TFC 703.2 - Opening protectives shall be maintained in an operative condition in accordance with NFPA 80. Fire doors and smoke barrier doors shall not be blocked or obstructed or otherwise made inoperable. _____ keep fire doors closed when not in use |
09/19/2008 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Violation | Portable Fire Extinguishers TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Non-required fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ Extinguishers shall be inspected and tagged in accordance with this code, or removed |
09/19/2008 | VIOL - FIRE PROTECTION SYSTEMS | DGREENLE | Violation | TFC 906.6 - Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. _____ clear obstruction to fire extinguisher - rear of showroom _____ move and re-mount fire extinguisher in an approved manner - stockroom |
09/19/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | Blocked exit: TFC 1003.6 - Means of egress continuity. Obstructions shall not be placed in the required width of a means of egress....The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear and maintain 28" exit path - stockroom _____ Clear and maintain 36" exit path - showroom to back exit hallway _____ Clear and maintain 36" exit path - back exit hallway |
09/19/2008 | VIOL - MEANS OF EGRESS | DGREENLE | Violation | MEANS OF EGRESS ILLUMINATION TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Repair or replace emergency lighting units |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02976
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/18/2008 | INSP - REINSPECTION | DGREENLE | Approved | still trying to get light repaired |