Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T08FR02976
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/19/2008 | VIOL - MEANS OF EGRESS | Violation | Blocked exit: TFC 1003.6 - Means of egress continuity. Obstructions shall not be placed in the required width of a means of egress....The required capacity of a means of egress system shall not be diminished along the path of egress travel. _____ Clear and maintain 28" exit path - stockroom _____ Clear and maintain 36" exit path - showroom to back exit hallway _____ Clear and maintain 36" exit path - back exit hallway |
|
09/19/2008 | VIOL - MEANS OF EGRESS | Violation | MEANS OF EGRESS ILLUMINATION TFC 1006.1 - Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. _____ Repair or replace emergency lighting units |