Case: T08FR02746
Case Details
Entered Date:
09/10/2008
Applicant:
BC LIMITED LLC
Description:
Full Fire Prevention Inspection. Claudette Myers 792-9882
Outstanding Inspections
Case Number: T08FR02746
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 3
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/10/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. _____1.Post the wording, "THIS DOOR BLOCKED", on the exterior side of the Northwest door. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
09/10/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. _____1.Post the above wording on the inside of the entrance/exit door. |
09/10/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. _____1.Remove all storage from the Fox Theatre exit access walkway located on the North and West side of your business. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02746
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |