Case: T08FR02742
Case Details
Entered Date:
09/10/2008
Applicant:
BC LIMITED LLC
Description:
Full Fire Prevention Inspection. Karen Rivera 903-0255
Outstanding Inspections
Case Number: T08FR02742
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/10/2008 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. _____1.Remove all combustable storage from around the water heater located in the kitchen. |
09/10/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1.All open spaces in the electrical panel located in the kitchen by the back door shall be coverd with an electrical blank. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
09/10/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1.Properly align the hood extinguishing system nozzles with the cooking equipment. |
09/10/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. _____1.Clean and remove all grease accumulation from the kitchen hood system and provide documentation of such work. |
09/10/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1.Remove the locking-bar and hardware from the west kitchen door. NOTE:Use a thumb-turn deadbolt to secure the door. |
09/10/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1.The exit sign located above the entrance/exit door shall be illuminated at all times. |
09/10/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____1.Remove all storage from obstructing the means of egress located on the outside of the kitchen door. |
09/10/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. Securing of compressed gas containers, cylinders and tanks shall be by one of the following method: 1. Securing containers, cylinders and tanks to a fixed object with one or more restraints. _____1.Secure the compressed gas cylinders located by the soda machine and in the kitchen. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02742
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/23/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson fire code violations have been corrected. |