Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

09/08/2008

Applicant:

TUCSON ST MARY'S PLAZA LLC

Description:

Full Fire Prevention Inspection. Kim Nguyen 884-7888

Outstanding Inspections

Case Number: T08FR02718
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
09/08/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____1.Remove the cube adapter located by the first nail station on the South wall. NOTE:Replace it with a fused multi-plug adapter.
09/08/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1.Remove the extension cord located by the washer and dryer. NOTE:Replace it with a fused multi-plug adapter. _____2.Remove the extension cord located in the waxing room on the East wall. NOTE:Replace it with a fused multi-plug adapter. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
09/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background. _____1.Post the above wording on or above the inside of the main entrance/exit door.
09/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1.Remove the surface bolt from the the East egress door.
09/08/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____1.Remove 1 of the 2 thumb-turn locks from the East security grill.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02718
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/22/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.