Case: T08FR02718

Parcel: 11615077H

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
09/08/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8.3 Locks and latches. Locks and latches shall
be permitted to prevent operation of doors where any of
the following exists:
2.2. A readily visible durable sign is posted on
the egress side on or adjacent to the door
stating: THIS DOOR TO REMAIN
UNLOCKED WHEN BUILDING IS
OCCUPIED. The sign shall be in letters 1
inch (25 mm) high on a contrasting background.

_____1.Post the above wording on or above the inside of the main entrance/exit door.
09/08/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or
surface bolts are not permitted.

_____1.Remove the surface bolt from the the East egress door.
09/08/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8.5 Unlatching. The unlatching of any door or
leaf shall not require more than one operation.

_____1.Remove 1 of the 2 thumb-turn locks from the East security grill.