Case: T08FR02712
Case Details
Entered Date:
09/08/2008
Applicant:
TUCSON ST MARY'S PLAZA LLC
Description:
Full Fire Prevention Inspection. Karen Brandon 624-5669
Outstanding Inspections
Case Number: T08FR02712
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2008 | VIOL - PRECAUTION AGAINST FIRE | JBURGE | Correction Required | TFC 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. _____1.All storage located in the stock room shall be maintained 18 inches below sprinkler head deflectors. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
| 09/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1.There are multiple extension cords being used for permanent wiring. Remove all extension cords and replace them with fused multi-plug adapters. |
| 09/08/2008 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. _____1.Replace the missing ceiling tile located above the south isle. |
| 09/08/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1.Remove the 2 surface bolts from the middle egress door located on the East side of the building. NOTE:Add a thumb-turn lock for more security. |
| 09/08/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____1.Remove all storage from obstructing the Southeast egress door. ______2.Remove all storage from obstructing the middle egress door on the east side of the building. _____3.Remove all storage from obstructing the Northeast egress door. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02712
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/22/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |