Case: T08FR02712

Parcel: 11615077K

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
09/08/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1028.3 Obstructions. A means of egress shall be free from
obstructions that would prevent its use.

_____1.Remove all storage from obstructing the Southeast egress door.

______2.Remove all storage from obstructing the middle egress door on the east side of the building.

_____3.Remove all storage from obstructing the Northeast egress door.
09/08/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or
surface bolts are not permitted.

_____1.Remove the 2 surface bolts from the middle egress door located on the East side of the building.
NOTE:Add a thumb-turn lock for more security.