Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/08/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____1.Remove all storage from obstructing the Southeast egress door. ______2.Remove all storage from obstructing the middle egress door on the east side of the building. _____3.Remove all storage from obstructing the Northeast egress door. |
|
| 09/08/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1.Remove the 2 surface bolts from the middle egress door located on the East side of the building. NOTE:Add a thumb-turn lock for more security. |