Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

09/08/2008

Applicant:

ITH SARO & SOY SAVY CP/RS

Description:

FULL FIRE INSPECTION

Outstanding Inspections

Case Number: T08FR02657
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
End Date Description Inspector Results Comments
09/08/2008 INSP - LIFE SAFETY MWAINWRI Violation 2006 IFC 605.1 INSTALL PLASTIC BLANKS IN ELECTRICAL PANEL. ELECTRICAL EQUIPMENT, WIRING AND HAZARDS 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used.
09/08/2008 INSP - LIFE SAFETY MWAINWRI Violation 2006 IFC 605.5 REMOVE THE EXTENSION CORD RUNNING ACROSS THE FLOOR IN THE KITCHEN. 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.
09/08/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 901.6 SERVICE FIRE EXTINGUISHER IN KITCHEN BY SINK SERVICE AND TAG HOOD SYSTEM 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective.
09/08/2008 VIOL - FIRE PROTECTION SYSTEMS MWAINWRI Violation 2006 IFC 904.11.5.2 INSTALL A K BOTTLE EXTINGUISHER IN KITCHEN AREA. 904.11.5.2 Class K portable fire extinguishers for deep fat fryers. When hazard areas include deep fat fryers, listed Class K portable fire extinguishers shall be provided as follows: 1. For up to four fryers having a maximum cooking medium capacity of 80 pounds (36.3 kg) each: One Class K portable fire extinguisher of a minimum 1.5 gallon ( 6 L) capacity.
09/08/2008 VIOL - MEANS OF EGRESS MWAINWRI Violation 2006 IFC 1008.1.8 REMOVE THE 2 DOUBLE KEYED LOCKS ON REAR DOOR AND REPLACE WITH A THUMB TURN 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02657
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/14/2009 INSP - FULL MWAINWRI Approved