Case: T08FR02657

Parcel: 12218017A


Addresses:

3860 E PIMA ST


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR02657

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
09/08/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 2006 IFC 904.11.5.2
INSTALL A K BOTTLE EXTINGUISHER IN KITCHEN AREA.

904.11.5.2 Class K portable fire extinguishers for
deep fat fryers. When hazard areas include deep fat fryers,
listed Class K portable fire extinguishers shall be
provided as follows:
1. For up to four fryers having a maximum cooking
medium capacity of 80 pounds (36.3 kg) each: One
Class K portable fire extinguisher of a minimum
1.5 gallon ( 6 L) capacity.
09/08/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 2006 IFC 901.6
SERVICE FIRE EXTINGUISHER IN KITCHEN BY SINK
SERVICE AND TAG HOOD SYSTEM

901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective.