Case: T08FR02523
Case Details
Entered Date:
08/26/2008
Applicant:
CENTURY THEATRES OF ARIZONA INC
Description:
Full Fire Prevention Inspection. Daniel Luke 620-0760
Outstanding Inspections
Case Number: T08FR02523
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/26/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1.All open spaces in the electrical service panel located in the employee break room shall have an approved electrical blank. _____2.All open spaces in the electrical service panels located in the large booth shall have an approved electrical blank. |
08/26/2008 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. _____1.Replace the missing ceiling tile located in the small booth. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg |
08/26/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1.Repair or replace the broken emergency lighting unit located in the Women's restroom located in the main lobby. _____2.Repair or replace the broken emergency lighting unit located on the east wall in the lobby. _____3.Repair or replace the broken emergency lighting unit located on the south wall in theatre #16. NOTE: The test button is broken. _____4.Repair or replace the broken emergency lighting unit located on the wall in the entrance area. NOTE: The test button is broken. _____5.Repair or replace the 2 broken emergency lighting units located on the wall in theatre # 13. NOTE: The test button is broken on one of the lighting units. _____6.Repair or replace the broken emergency lighting unit located on the wall between the doors of theatre #11. |
08/26/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with Section 1011. _____1.Repair or replace the exit sign located in theatre #16. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02523
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/06/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |