HOOD SYSTEM INSPECTION
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR02209
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/31/2008 | VIOL - FIRE PROTECTION SYSTEMS | RSPANGLE | Approved | 1.) TFC 904.2.1 THE REGULAR SPRINKLER HEADS ARE NOT ACCEPTABLE FOR A TYPE 1 HOOD IN THE AMBASSADOR KITCHEN. WATER CANNOT BE USED AS AN EXTINGUISHING AGENT FOR DEEP FAT FRYERS, STOVE AND GRILL. AN APPROVED UL300 EXTINGUISHING SYSTEM MUST BE INSTALLED BY A QUALIFIED COMPANY AFTER APPLYING FOR AND RECEIVING A PERMIT. |