Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T08FR02209
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
03/24/2009 | VIOL - FIRE PROTECTION SYSTEMS | Approved | UL 300 SYSTEM WAS INSTALLED AND APPROVED BY SYSTEM DESIGN. | |
07/31/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 1.) TFC 904.2.1 THE REGULAR SPRINKLER HEADS ARE NOT ACCEPTABLE FOR A TYPE 1 HOOD IN THE AMBASSADOR KITCHEN. WATER CANNOT BE USED AS AN EXTINGUISHING AGENT FOR DEEP FAT FRYERS, STOVE AND GRILL. AN APPROVED UL300 EXTINGUISHING SYSTEM MUST BE INSTALLED BY A QUALIFIED COMPANY AFTER APPLYING FOR AND RECEIVING A PERMIT. |