Case: T08FR02209

Parcel: 11011176E


Addresses:

2500 N ROSEMONT BL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR02209

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
03/24/2009 VIOL - FIRE PROTECTION SYSTEMS Approved UL 300 SYSTEM WAS INSTALLED AND APPROVED BY SYSTEM DESIGN.
07/31/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 1.) TFC 904.2.1 THE REGULAR SPRINKLER HEADS ARE NOT ACCEPTABLE FOR A TYPE 1 HOOD IN THE AMBASSADOR KITCHEN. WATER CANNOT BE USED AS AN EXTINGUISHING AGENT FOR DEEP FAT FRYERS, STOVE AND GRILL. AN APPROVED UL300 EXTINGUISHING SYSTEM MUST BE INSTALLED BY A QUALIFIED COMPANY AFTER APPLYING FOR AND RECEIVING A PERMIT.