General Inspection

Outstanding Inspections

Case Number: T08FR02192
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
08/21/2008 INSP - FULL JBEZEL Correction Required Added violation: In order to store tires in the back storage room the sprinkler sysytem must be properly designed with proper sized piping for adequate coverage for such materials as tires. (IFC 901.6) Have a sprinkler contracter examine and submit plans and make necessary alterations.