Case: T08FR02192
Case Details
Entered Date:
07/29/2008
Applicant:
CENTRAL ONE INC
Description:
General Inspection
Outstanding Inspections
Case Number: T08FR02192
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/21/2008 | INSP - FULL | JBEZEL | Correction Required | Added violation: In order to store tires in the back storage room the sprinkler sysytem must be properly designed with proper sized piping for adequate coverage for such materials as tires. (IFC 901.6) Have a sprinkler contracter examine and submit plans and make necessary alterations. |