Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T08FR02192
Inspection Description - INSP - FULL
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2009 | INSP - FULL | Correction Required | Checked tiles over tire storage in recheck. They were wet in last storm and are down again. Management has a roofer fixing the leak starting Sunday. I gave them two more weeks to have leak fixed and tiles in place. Every recheck has had the same issues. The tiles go up, and water leaks during storms bring them down. | |
| 08/21/2008 | INSP - FULL | Correction Required | Added violation: In order to store tires in the back storage room the sprinkler sysytem must be properly designed with proper sized piping for adequate coverage for such materials as tires. (IFC 901.6) Have a sprinkler contracter examine and submit plans and make necessary alterations. | |
| 08/20/2008 | INSP - FULL | Correction Required | Spoke with manager regarding tire storage in back room. Researched sprinkler system down town and discussed with Harvey Brown. email correspondance as follows: Please do not store tires here unless the piping is changed. The piping in this area is sized for Light Hazard (.10 GPM per square foot). This is less then a third of the demand for the tire storage area. Just wouldn't be comfortable the sprinkler system might not be overwhelmed by an incident. Would need a (sprinkler) contractor to submit a plan and new hydraulic calculations to verify the size of piping required for tire storage. Thanks >>> John Bezel 08/20/2008 2:39 PM >>> I have a question I meant to ask you yesterday. Regarding the Discount tire place wanting to store tires on racks in that one room that has too small of a sprinkler main. They cannot store tires on racks back there, but can they store tires in neat stacks on the floor back there as long as sprinkler head clearance is adequate? Or are they not allowed to store any tires back there at all until the sprinkler piping is changed? They currently store tires back there, but they would prefer to put them on racks. Thanks. Will F/U. Gave report to Inspector Sprenger. Inspecter Sprenger to take over case. |
|
| 07/29/2008 | INSP - FULL | Correction Required | The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications). ___1. PROBLEM: Emergency light not functioning in repair bay near office door. TFC REFERENCE: 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. REQUIRED CORRECTION: Check all emergency lighting units and repair where necessary. ___2. PROBLEM: Ceiling tiles missing from tire storage room and hole in ceiling with exposed insulation in repair area thus allowing smoke and flames to travel into attic space and above sprinkler heads. TFC REFERENCE: 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire. REQUIRED CORRECTION: Have hole in ceiling repaired and replace missing ceiling tiles. ___3. PROBLEM: Tire storage area exit is blocked with stacked tires. The roll up fire door does not count as an exit TFC REFERENCE: 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter. Obstructions shall not be placed in the required width of a means of egress except projections permitted by this chapter. The required capacity of a means of egress system shall not be diminished along the path of egress travel. REQUIRED CORRECTION: Must have one unobstructed exit clearly visible in tire storage area. ___4. PROBLEM: Orage extension cord used for soda pop machine. TFC REFERENCE: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. REQUIRED CORRECTION: Any and all extension cords must be replaced with approved GFI power strips. ___5. PROBLEM: Damaged exit sign in riser room. TFC REFERENCE: 1011.2 Illumination. Exit signs shall be internally or externally illuminated. REQUIRED CORRECTION: Repair damaged exit sign so that it is functioning properly. ___6. PROBLEM: Storage around sprinkler riser blocking access to sprinkler system. TFC REFERENCE: 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner thatwould prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. REQUIRED CORRECTION: Provide proper access to sprinkler equipment. ___7. PROBLEM: Storage blocking access to electrical panel. TFC REFERENCE: 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space. REQUIRED CORRECTION: Provide proper clearance around electrical panel. ___8. PROBLEM: Need sign on door on outside indicating location of sprinkler equipment. TFC REFERENCE: 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. REQUIRED CORRECTION: Have riser room sign affixed to outside of riser room door. ___9. PROBLEM: Exit at back of tire rack storage and in riser room has double keyed cylinder locks. TFC REFERENCE:1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. REQUIRED CORRECTION: Replace with thumb turn locks. ___10. PROBLEM: One tire rack in the back appears to have questionable clearance from sprinkler head. TFC REFERENCE: 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings or a minimum of 18 inches (457 mm) below sprinkler head deflectors in sprinklered areas of buildings. REQUIRED CORRECTION: Do not stack tires too close to sprinkler heads. The Tucson Fire Department is committed to the protection of your property and your life safety.Your help as a business owner and as a citizen is greatly appreciated. Property Representative Signature: _________________________. Fire Inspector Signature: _________________________(791-4502). Reinspection Date: ___/___/___ or later. ___Approved ___Not Approved |