Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/23/2008

Applicant:

H L F PROPERTIES INC

Description:

Full Fire Prevention Inspection. Turtle Diane Bates 887-2643

Outstanding Inspections

Case Number: T08FR02103
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 6
End Date Description Inspector Results Comments
07/23/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. _____1. Repair the broken electrical outlet located by the couch in admin. ________________________________________________ (John E. Bieg, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
07/23/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1. Remove all extension cords and replace them with fused multi-plug adapters.
07/23/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1. The electrical outlet located by the admin desk shall have an approved cover.
07/23/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____1. Remove 1 of the 2 thumb-turn locks from the Southwest egress door. _____2. Remove 1 of the 2 thumb-turn locks from the Southeast egress doors.
07/23/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. The exit sign located above the Southeast exit door shall be illuminated at all times.
07/23/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency when the areas served by such exits are occupied. Security devices affecting means of egress shall be subject to approval of the fire code official. _____1. Remove all merchandise storage from obstructing the Northwest egress door.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR02103
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/06/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.