Case: T08FR01945
Case Details
Entered Date:
07/16/2008
Applicant:
SE KOLB LLC
Description:
need extuingher at hood please see attached
Outstanding Inspections
Case Number: T08FR01945
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 3
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/16/2008 | INSP - FULL | ALOPEZ | Correction Required | Need extuingher at hood? see attached |
| 07/23/2008 | INSP - LIFE SAFETY | EGRIFFIN | Violation | |
| 07/23/2008 | INSP - LIFE SAFETY | EGRIFFIN | Violation | Currently kitchen hood extinguishing system is not in compliance with fire code requirements. This is indicated by the semi annual hood system report and a non-compliance tag on manual activation device. The fire code requires: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion. Please ensure current certificate or tags are affixed to manual activation devices by 8-6-08 |