Case: T08FR01945

Parcel: 13419042A


Addresses:

7102 E BROADWAY BL


Inspection Status: Violation

Inspection History: INSP - LIFE SAFETY

Case Number - T08FR01945

Inspection Description - INSP - LIFE SAFETY

Inspection Status - Violation

Date Description Inspector Results Comments
07/23/2008 INSP - LIFE SAFETY Violation
07/23/2008 INSP - LIFE SAFETY Violation Currently kitchen hood extinguishing system is not in compliance with fire code requirements. This is indicated by the semi annual hood system report and a non-compliance tag on manual activation device.

The fire code requires:

901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed.
904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. Inspection shall be by qualified individuals, and a certificate of inspection shall be forwarded to the fire code official upon completion.

Please ensure current certificate or tags are affixed to manual activation devices by 8-6-08