Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/15/2008

Applicant:

STELLE KENT VAN

Description:

Night inspections.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01906
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/15/2008 INSP - NIGHT RDUARTE Approved TFC 1008.1 LOCKS & LATCHES - All exit doors require panic hardware & may not have any additional locking devices affixed. - Remove deadbolts & slide bolts from exit doors. - Install "This Door to Remain Unlocked while Building is Occupied" Signage at front door (main entrance)- Both door leafs must be unlocked. TFC 1011 EXIT SIGNS - Repair illumination of patio exit sign TFC 3003 COMPRESSED GAS CYLINDERS - Chain/Secure all compressed gas cylinders (Kitchen) TFC 3809 LPA - Remove Propane cylinders from mushroom heaters (2) in kitchen. Cylinders must be stored outside the building. Insp Glenn D'Auria (MA16). TFC 603.1 ELECTRICAL HAZARDS - Install missing outlet (J-box) cover plates in Kit & at south bar. Also, replace extension cord at steps w/permanent wire & conduit. TFC 102.7 Gas supply to cooking appliances must be "capped off".