Case: T08FR01906

Parcel: 124061720


Addresses:

136 N PARK AV


Inspection Status: Approved

Inspection History: INSP - NIGHT

Case Number - T08FR01906

Inspection Description - INSP - NIGHT

Inspection Status - Approved

Date Description Inspector Results Comments
07/15/2008 INSP - NIGHT Approved TFC 1008.1 LOCKS & LATCHES

- All exit doors require panic hardware & may not have any additional locking devices affixed.
- Remove deadbolts & slide bolts from exit doors.
- Install "This Door to Remain Unlocked while Building is Occupied" Signage at front door (main entrance)- Both door leafs must be unlocked.

TFC 1011 EXIT SIGNS

- Repair illumination of patio exit sign

TFC 3003 COMPRESSED GAS CYLINDERS

- Chain/Secure all compressed gas cylinders (Kitchen)

TFC 3809 LPA

- Remove Propane cylinders from mushroom heaters (2) in kitchen. Cylinders must be stored outside the building. Insp Glenn D'Auria (MA16).


TFC 603.1 ELECTRICAL HAZARDS

- Install missing outlet (J-box) cover plates in Kit & at south bar. Also, replace extension cord at steps w/permanent wire & conduit.

TFC 102.7
Gas supply to cooking appliances must be "capped off".