Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

07/09/2008

Applicant:

MASSAPEQUA ASSOCIATES LLC

Description:

Full fire Prevention Inspection. Ashleigh Read 884-8890

Outstanding Inspections

Case Number: T08FR01844
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
07/09/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____1. Remove the cube adapter located by the prep table.
07/09/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____1. Service, tag and mount the portable fire extinguisher located in the kitchen. ________________________________________________ (John E. Bieg, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector John E. Bieg Re-inspection scheduled on or after _____/_____/_____ Call Inspector Bieg at 235-4785 or 791-4502, if you have any further questions. Thank you. All noted Tucson Fire Code violations have been corrected: _____/_____/_____ ______________________ John E. Bieg
07/09/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____1. Remove the lock bar and lock bar hardware from the exit door located in the kitchen. _____2. Remove the double keyed lock from the exit door located in the kitchen and replace it with a thumb-turn lock.
07/09/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. _____1. Remove all 4 surface bolts from the exit door located in the kitchen.
07/09/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than 5 foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. _____1. The exit sign located in the dinning area shall have emergency back-up power.
07/09/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system. _____1. Repair the emergency lighting unit located on the North wall in the dinning area. _____2. Repair the emergency lighting unit located on the South wall in the dinning area.
07/09/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____1. Secure the compressed gas cylinders located in the kitchen to the wall or a fixed object with one or more restraints.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01844
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/14/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.