Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR01844

Parcel: 10321342A


Addresses:

2110 W GRANT RD


Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR01844

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
07/09/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated. The face of an exit sign illuminated
from an external source, shall have an intensity of not less than
5 foot-candles (54 lux). Internally illuminated signs shall provide
equivalent luminance and be listed for the purpose.

_____1. The exit sign located in the dinning area shall have emergency back-up power.
07/09/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system.

_____1. Repair the emergency lighting unit located on the North wall in the dinning area.

_____2. Repair the emergency lighting unit located on the South wall in the dinning area.
07/09/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8.4 Bolt locks. Manually operated flush bolts or
surface bolts are not permitted.

_____1. Remove all 4 surface bolts from the exit door located in the kitchen.
07/09/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

_____1. Remove the lock bar and lock bar hardware from the exit door located in the kitchen.

_____2. Remove the double keyed lock from the exit door located in the kitchen and replace it with a thumb-turn lock.