Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Case: T08FR01800
Case Details
Entered Date:
07/03/2008
Applicant:
TMC FOUNDATION
Description:
SPRINKLER SYSTEM INSPECTION
Outstanding Inspections
Case Number: T08FR01800
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2008 | VIOL - FIRE PROTECTION SYSTEMS | RSPANGLE | Violation | TFC 901.6 THE FOLLOWING SPRINKLER SYSTEM DEFICIENCIES MUST BE CORRECTED: 1.) ON RISER # 30, NORTH STORAGE AREA TWO SPRINKLER HEADS IN WRONG POSITION. PENDANTS IN UPRIGHT POSITION. 2.) ALAMO BUILDING: A.) THERE IS A PADDLE TYPE WATER FLOW SWITCH ON THE RISER FOR A DELUGE SYSTEM. THE PADDLE MUST BE REMOVED AND HUNG IN A VISIBLE PLACE ON THE RISER. B.) A HYDRAULIC NAME PLATE NEEDS TO BE IN PLACE ON THE RISER FOR THE WET SYSTEM. 3.) M.R.I. BUILDING: THE PRESSURE SWITCH FOR WATER FLOW NEEDS TO OPERATE SO THAT A GENERAL ALARM SOUNDS. |