Case: T08FR01800

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR01800

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
07/03/2008 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 901.6 THE FOLLOWING SPRINKLER SYSTEM DEFICIENCIES MUST BE CORRECTED:
1.) ON RISER # 30, NORTH STORAGE AREA TWO SPRINKLER HEADS IN WRONG POSITION. PENDANTS IN UPRIGHT POSITION.
2.) ALAMO BUILDING: A.) THERE IS A PADDLE TYPE WATER FLOW SWITCH ON THE RISER FOR A DELUGE SYSTEM. THE PADDLE MUST BE REMOVED AND HUNG IN A VISIBLE PLACE ON THE RISER.
B.) A HYDRAULIC NAME PLATE NEEDS TO BE IN PLACE ON THE RISER FOR THE WET SYSTEM.
3.) M.R.I. BUILDING: THE PRESSURE SWITCH FOR WATER FLOW NEEDS TO OPERATE SO THAT A GENERAL ALARM SOUNDS.