Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T08FR01800
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/03/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6 THE FOLLOWING SPRINKLER SYSTEM DEFICIENCIES MUST BE CORRECTED: 1.) ON RISER # 30, NORTH STORAGE AREA TWO SPRINKLER HEADS IN WRONG POSITION. PENDANTS IN UPRIGHT POSITION. 2.) ALAMO BUILDING: A.) THERE IS A PADDLE TYPE WATER FLOW SWITCH ON THE RISER FOR A DELUGE SYSTEM. THE PADDLE MUST BE REMOVED AND HUNG IN A VISIBLE PLACE ON THE RISER. B.) A HYDRAULIC NAME PLATE NEEDS TO BE IN PLACE ON THE RISER FOR THE WET SYSTEM. 3.) M.R.I. BUILDING: THE PRESSURE SWITCH FOR WATER FLOW NEEDS TO OPERATE SO THAT A GENERAL ALARM SOUNDS. |