Case Details

Status:

FIELD

Type:

INSPECTION

Entered Date:

06/26/2008

Applicant:

RESEDA COLONIA LLC 2.21% & LINCOLN COLONIA LLC

Description:

SPRINKLER INSPECTION

Completed Inspections

Case Status: FIELD
Case Number: T08FR01716
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/26/2008 INSP - FULL EDESCHAI Approved 1) tHE MAIN DRAINS ON THE RISER ARE NOT CLOSING AND NEED TO BE REPAIRED 2) THE INSPECTORS TEST VALVE LEAKS AND NEEDS REPAIR 3) THE FIRE DEPARTMENT CONNECTION NEEDS PROTECTIVE CAPS INSTALLED 4) THE TAMPER CONTROL VALVE AT THE RISER DID NOT RESET AND NEEDS REPAIR 5) tHE FIRE DEPT. CONNECTION NEEDS TO BE BRACED AND STRAIGNTENED OUT 6) tHE S/W COOLER HAS CORRODED HEADS, REPLACE