Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Compliance
Inspection History: INSP - FULL
Case Number - T08FR01716
Inspection Description - INSP - FULL
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/26/2008 | INSP - FULL | Compliance | 1) tHE MAIN DRAINS ON THE RISER ARE NOT CLOSING AND NEED TO BE REPAIRED 2) THE INSPECTORS TEST VALVE LEAKS AND NEEDS REPAIR 3) THE FIRE DEPARTMENT CONNECTION NEEDS PROTECTIVE CAPS INSTALLED 4) THE TAMPER CONTROL VALVE AT THE RISER DID NOT RESET AND NEEDS REPAIR 5) tHE FIRE DEPT. CONNECTION NEEDS TO BE BRACED AND STRAIGNTENED OUT 6) tHE S/W COOLER HAS CORRODED HEADS, REPLACE |