Case: T08FR01716

Parcel: 11460019C

Inspection Status: Compliance

Inspection History: INSP - FULL

Case Number - T08FR01716

Inspection Description - INSP - FULL

Inspection Status - Compliance

Date Description Inspector Results Comments
06/26/2008 INSP - FULL Compliance 1) tHE MAIN DRAINS ON THE RISER ARE NOT CLOSING AND NEED TO BE REPAIRED

2) THE INSPECTORS TEST VALVE LEAKS AND NEEDS REPAIR

3) THE FIRE DEPARTMENT CONNECTION NEEDS PROTECTIVE CAPS INSTALLED

4) THE TAMPER CONTROL VALVE AT THE RISER DID NOT RESET AND NEEDS REPAIR

5) tHE FIRE DEPT. CONNECTION NEEDS TO BE BRACED AND STRAIGNTENED OUT

6) tHE S/W COOLER HAS CORRODED HEADS, REPLACE