Case: T08FR01692
Case Details
Entered Date:
06/24/2008
Applicant:
CENTRO NP HOLDINGS 1 SPE LLC
Description:
Full fire inspection.
Outstanding Inspections
Case Number: T08FR01692
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 19
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/24/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 505.1- Address numbers. Post the building address numbers on the side of the building facing River Rd. The address numbers shall be 12 inches tall, durable and visible from the street. |
06/24/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 508.5.4- Obstruction. Remove all storage located around the sprinkler system control valves and riser pipe. |
06/24/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6- Unapproved conditions. All open spaces in the electrical service panels shall be covered with an electrical blank, located in the kitchen. |
06/24/2008 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1- Maintenance. Repair the hole in the wall located in the office |
06/24/2008 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1- Maintenance. Replace the missing ceiling tiles located in the office. |
06/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection testing and maintenance. Replace the missing sprinkler system fire department connection coupling cover. |
06/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection testing and maintenance. Service, test and tag the automatic sprinkler system or provide documentation of such work within the last 12 months. |
06/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection, testing and maintenance. Add, relocate and align the hood extinguishing system nozzles to properly cover all cooking equipment. |
06/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection, testing and maintenance. All portable fire extinguishers shall be tested, serviced and mounted on a bracket. |
06/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 903.4- Sprinkler system moitoring and alarms. The control valve for the automatic sprinkler system shall be locked in the open position with a chain and padlock. |
06/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.6.3- Cleaning. Clean and remove all grease and other accumulation from the hood system. |
06/24/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 904.11.7- The gyro machine shall be at least 16 inches from the deep fat fryer. |
06/24/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8- Door operations. Remove the double-keyed lock from the door that leads to the patio. |
06/24/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.4- Bolt locks. Remove the surface bolts from the exit door and gate located in the kitchen. |
06/24/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3- Exit sign illumination. The exit sign located by the main entrance/exit door shall be illuminated and shall have emergency back-up power. |
06/24/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3- Exit sign illumination. The exit sign located by the west exit door shall be illuminated and shall have emergency back-up power. |
06/24/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Illumination emergency power. Repair or replace the broken emergency lighting unit located on the ceiling above the entrance/exit door. |
06/24/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.2- Reliability. Repair or replace the broken panic hardware located on the exit door in the kitchen. |
06/24/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3- Securing compressed gas containers, cylinders and tanks. All compressed gas cylinders located by the ice machine shall be properly secured with a chain or strap and anchored to the wall or fixed object. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01692
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/27/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |