Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/24/2008

Applicant:

CENTRO NP HOLDINGS 1 SPE LLC

Description:

Full fire inspection.

Outstanding Inspections

Case Number: T08FR01692
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 19
End Date Description Inspector Results Comments
06/24/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 505.1- Address numbers. Post the building address numbers on the side of the building facing River Rd. The address numbers shall be 12 inches tall, durable and visible from the street.
06/24/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 508.5.4- Obstruction. Remove all storage located around the sprinkler system control valves and riser pipe.
06/24/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6- Unapproved conditions. All open spaces in the electrical service panels shall be covered with an electrical blank, located in the kitchen.
06/24/2008 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1- Maintenance. Repair the hole in the wall located in the office
06/24/2008 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1- Maintenance. Replace the missing ceiling tiles located in the office.
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Inspection testing and maintenance. Replace the missing sprinkler system fire department connection coupling cover.
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Inspection testing and maintenance. Service, test and tag the automatic sprinkler system or provide documentation of such work within the last 12 months.
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Inspection, testing and maintenance. Add, relocate and align the hood extinguishing system nozzles to properly cover all cooking equipment.
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Inspection, testing and maintenance. All portable fire extinguishers shall be tested, serviced and mounted on a bracket.
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 903.4- Sprinkler system moitoring and alarms. The control valve for the automatic sprinkler system shall be locked in the open position with a chain and padlock.
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3- Cleaning. Clean and remove all grease and other accumulation from the hood system.
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.7- The gyro machine shall be at least 16 inches from the deep fat fryer.
06/24/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8- Door operations. Remove the double-keyed lock from the door that leads to the patio.
06/24/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.4- Bolt locks. Remove the surface bolts from the exit door and gate located in the kitchen.
06/24/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3- Exit sign illumination. The exit sign located by the main entrance/exit door shall be illuminated and shall have emergency back-up power.
06/24/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3- Exit sign illumination. The exit sign located by the west exit door shall be illuminated and shall have emergency back-up power.
06/24/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Illumination emergency power. Repair or replace the broken emergency lighting unit located on the ceiling above the entrance/exit door.
06/24/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2- Reliability. Repair or replace the broken panic hardware located on the exit door in the kitchen.
06/24/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3- Securing compressed gas containers, cylinders and tanks. All compressed gas cylinders located by the ice machine shall be properly secured with a chain or strap and anchored to the wall or fixed object.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01692
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/27/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.