Case: T08FR01692

Parcel: 10509547A


Addresses:

95 W RIVER RD


Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR01692

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6- Inspection testing and maintenance. Replace the missing sprinkler system fire department connection coupling cover.
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6- Inspection testing and maintenance. Service, test and tag the automatic sprinkler system or provide documentation of such work within the last 12 months.
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6- Inspection, testing and maintenance. Add, relocate and align the hood extinguishing system nozzles to properly cover all cooking equipment.
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 903.4- Sprinkler system moitoring and alarms. The control valve for the automatic sprinkler system shall be locked in the open position with a chain and padlock.
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 904.11.6.3- Cleaning. Clean and remove all grease and other accumulation from the hood system.
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 904.11.7- The gyro machine shall be at least 16 inches from the deep fat fryer.
06/24/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6- Inspection, testing and maintenance. All portable fire extinguishers shall be tested, serviced and mounted on a bracket.