Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

06/20/2008

Applicant:

CNL INCOME FEC TUCSON LLC

Description:

Full Fire Inspection.

Outstanding Inspections

Case Number: T08FR01660
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 17
End Date Description Inspector Results Comments
06/20/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 508.5.4- Obstruction. Remove the bush from obstructing the fire department sprinkler connection located just north of the building.
06/20/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 510.1- Identification. Post a sign on the riser room door stating, "RISER ROOM."
06/20/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1- Abatement of electrical hazards. All open spaces located in the electrical service panel located in the upper storage room by the laser tag ramp shall be covered.
06/20/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5- Extension cords. Remove all extension cords used for permanent wiring in the upstairs office. NOTE:Replace the extension cords with fused power strips pluged directly into an electrical outlet.
06/20/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5- Extension cords. Remove all extension cords used for permanent wiring that power the arcade games.
06/20/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5- Extension cords. Remove the extension cords used to power the carousel.
06/20/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 609.2- Where required. A type 1 hood system shall be installed over the pizza conveyor ovens.
06/20/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Inspection, testing and maintenance. Service, test and tag the fire alarm system or provide documentation of the currect inspection.
06/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3- Exit sign illumination. All exit signs located in the laser tag room shall be internally or externally illuminated at all times.
06/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3- Exit sign illumination. The exit sign located above the west exit doors in the lobby shall be internally or externally illuminated at all times.
06/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3- Exit sign illumination. The exit sign located at the top of the laser tag ramp shall be internally or externally illuminated at all times.
06/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Illumination emergency power. I was unable to check the emergency lighting unit located in the women's restroom. Test the lighting unit. If the lighting unit does not illuminate when tested replace or repair the unit.
06/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Illumination emergency power. Repair the broken emergency lighting unit located by the laser tag ramp.
06/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Illumination emergency power. Repair the broken emergency lighting unit located in the laser pack room.
06/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Illumination emergency power. Repair the broken emergency lighting unit located on the 3rd level back wall.
06/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Illumination emergency power. Repair the broken emergency lighting unit located on the second level laser room back wall.
06/20/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Illumination emergency power. Repair the emergency lighting unit located on the front wall of the main building.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01660
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
09/04/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.