Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T08FR01660
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/20/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.5- Illumination emergency power. Repair the broken emergency lighting unit located by the laser tag ramp. | |
06/20/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.3- Exit sign illumination. The exit sign located at the top of the laser tag ramp shall be internally or externally illuminated at all times. | |
06/20/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.5- Illumination emergency power. Repair the broken emergency lighting unit located in the laser pack room. | |
06/20/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.5- Illumination emergency power. Repair the broken emergency lighting unit located on the 3rd level back wall. | |
06/20/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.5- Illumination emergency power. Repair the broken emergency lighting unit located on the second level laser room back wall. | |
06/20/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.3- Exit sign illumination. All exit signs located in the laser tag room shall be internally or externally illuminated at all times. | |
06/20/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.3- Exit sign illumination. The exit sign located above the west exit doors in the lobby shall be internally or externally illuminated at all times. | |
06/20/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.5- Illumination emergency power. Repair the emergency lighting unit located on the front wall of the main building. | |
06/20/2008 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.5- Illumination emergency power. I was unable to check the emergency lighting unit located in the women's restroom. Test the lighting unit. If the lighting unit does not illuminate when tested replace or repair the unit. |