Case: T08FR01524
Case Details
Entered Date:
06/13/2008
Applicant:
PHOENIX DOBSON LLC
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR01524
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/13/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 510.1- Identification. Post a sign on the outside of the riser room door stating," RISER ROOM." |
| 06/13/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.1- Abatement of electrical hazards. Remove the tape from the electrical panel breaker switches, located by the roll-up door in the stock room. |
| 06/13/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3- Working space and clearance. Remove all storage from obstructing the electrical service panels located by the roll-up door in the stock room, and by the sprinkler system riser room. |
| 06/13/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5- Extension cords. Remove the extension cords located in the security office. |
| 06/13/2008 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1- Maintenance. Replace the missing ceiling tiles located in the security office and above the cookie section on the sales floor, and by the roll-up door in the stock room. |
| 06/13/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 906.7- Hangers and brackets. The portable fire extinguisher located behind the north counter shall be mounted on a hanger or bracket. |
| 06/13/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8- Door operations. Remove the double-keyed lock form the northwest exit door. NOTE:Replace the double-keyed lock with a thumb-turn lock. |
| 06/13/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3- Locks and latches. Post the wording, "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" on the inside of the entrance/exit door. |
| 06/13/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.3- Exit sign illumination. The exit signs located above the exit doors shall be illuminated at all times. |
| 06/13/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- Illumination emergency power. Repair the 2 broken emergency lighting units located on the north and south wall. |
| 06/13/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1028.2- Reliability. Remove the storage from obstructing the northwest exit door. |
| 06/13/2008 | VIOL - HIGH PILED COMBUSTIBLES | JBURGE | Correction Required | TFC 2305.4- Aisle maintenance. A minimum unobstructed aisle width of 24 inches shall be maintained in the stock room. |
| 06/13/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3- Securing compressed gas containers, cylinders and tanks. The compressed gas cylinders located behind the north counter shall be secured with a chain or strap, and anchored to the wall or fixed object. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01524
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |