Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/13/2008

Applicant:

PHOENIX DOBSON LLC

Description:

Full Inspection.

Outstanding Inspections

Case Number: T08FR01524
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date Description Inspector Results Comments
06/13/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 510.1- Identification. Post a sign on the outside of the riser room door stating," RISER ROOM."
06/13/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1- Abatement of electrical hazards. Remove the tape from the electrical panel breaker switches, located by the roll-up door in the stock room.
06/13/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3- Working space and clearance. Remove all storage from obstructing the electrical service panels located by the roll-up door in the stock room, and by the sprinkler system riser room.
06/13/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5- Extension cords. Remove the extension cords located in the security office.
06/13/2008 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1- Maintenance. Replace the missing ceiling tiles located in the security office and above the cookie section on the sales floor, and by the roll-up door in the stock room.
06/13/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7- Hangers and brackets. The portable fire extinguisher located behind the north counter shall be mounted on a hanger or bracket.
06/13/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8- Door operations. Remove the double-keyed lock form the northwest exit door. NOTE:Replace the double-keyed lock with a thumb-turn lock.
06/13/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3- Locks and latches. Post the wording, "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" on the inside of the entrance/exit door.
06/13/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3- Exit sign illumination. The exit signs located above the exit doors shall be illuminated at all times.
06/13/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Illumination emergency power. Repair the 2 broken emergency lighting units located on the north and south wall.
06/13/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2- Reliability. Remove the storage from obstructing the northwest exit door.
06/13/2008 VIOL - HIGH PILED COMBUSTIBLES JBURGE Correction Required TFC 2305.4- Aisle maintenance. A minimum unobstructed aisle width of 24 inches shall be maintained in the stock room.
06/13/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3- Securing compressed gas containers, cylinders and tanks. The compressed gas cylinders located behind the north counter shall be secured with a chain or strap, and anchored to the wall or fixed object.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01524
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
07/02/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.