Case: T08FR01524

Parcel: 10609062C

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
06/13/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8.3- Locks and latches. Post the wording, "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" on the inside of the entrance/exit door.
06/13/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.3- Exit sign illumination. The exit signs located above the exit doors shall be illuminated at all times.
06/13/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.8- Door operations. Remove the double-keyed lock form the northwest exit door.
NOTE:Replace the double-keyed lock with a thumb-turn lock.
06/13/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1028.2- Reliability. Remove the storage from obstructing the northwest exit door.
06/13/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.5- Illumination emergency power. Repair the 2 broken emergency lighting units located on the north and south wall.