Description:

Full Inspection.

Outstanding Inspections

Case Number: T08FR01523
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date Description Inspector Results Comments
06/13/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.1- Ceiling clearance. Storage shall be maintained a minimum of 18 inches below sprinkler head deflectors located in the kitchen freezer.
06/13/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.3- Working space and clearance. Remove all storage from obstructing the electrical service panel located in the kitchen.
06/13/2008 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1- Maintenance. Replace the missing ceiling tiles located in the produce back room.
06/13/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Inspection testing and maintenance. Clean and remove all accumulation of grease and lint from the sprinkler heads located in the kitchen area.
06/13/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Inspection testing and maintenance. Properly align the hood extinguishing system nozzles with the cooking equipment located in the kitchen.
06/13/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Inspection testing and maintenance. Remove the hanging material from the sprinkler head located in the dairy cooler.
06/13/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 901.6- Inspection testing and maintenance. Service and test the fire alarm system or provide documentation of such work being done within the last year.
06/13/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.5.2- Class K portable fire extinguishers for deep fat fryers. A class K portable fire extinguisher shall be provided within 30 feet of all fryers.
06/13/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 904.11.6.3- Cleaning. Clean and remove all grease accumulation from the hood systems.
06/13/2008 VIOL - FIRE PROTECTION SYSTEMS JBURGE Correction Required TFC 906.7- Hangers and brackets. Mount an extinguisher on the bracket located by the north exit doors next to the beer cooloer.
06/13/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.8.3- Locks and latches. Post the wording, " THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED." on the inside of the two automatic entry/exit doors on the east side of the building.
06/13/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.2- Reliability. Repair the broken door hardware for the north exit door located in the stock room near produce.
06/13/2008 VIOL - COMPRESSED GASES JBURGE Correction Required TFC 3003.5.3- Securing compressed gas containers, cylinders and tanks. The helium cylinders located in the produce back room shall be secured with a chain or strap and anchored to the wall or fixed object.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR01523
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/26/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.