Description:

fire inspection

Completed Inspections

Case Status: FIELD
Case Number: T08FR01402
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
06/03/2008 INSP - FULL EDESCHAI Approved 1) Sprinkler heads in the front area inside of the partition exceed the allowable distance from the obstruction, additional sprinklers shall be added for correct coverage 2) In the kitchen there are numerous sprinklers loaded with grease. They shall be changed out. 3) The fire sprinkler riser shall be kept free of all storage 4) The spare head box is in need of a special wrewnch to change out sprinkler heads