Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Compliance
Inspection History: INSP - FULL
Case Number - T08FR01402
Inspection Description - INSP - FULL
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/03/2008 | INSP - FULL | Compliance | 1) Sprinkler heads in the front area inside of the partition exceed the allowable distance from the obstruction, additional sprinklers shall be added for correct coverage 2) In the kitchen there are numerous sprinklers loaded with grease. They shall be changed out. 3) The fire sprinkler riser shall be kept free of all storage 4) The spare head box is in need of a special wrewnch to change out sprinkler heads |