Case: T08FR01254
Case Details
Entered Date:
05/16/2008
Applicant:
CHILD PARENT CENTERS
Description:
sprinkler inspection, business inspection
Outstanding Inspections
Case Number: T08FR01254
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/16/2008 | INSP - FULL | EDESCHAI | Correction Required | 1) 901.6 Where sprinklers have been in service for 50 years, they shall be replaced , or samples from one or more sample areas shall be tested. 2) 605.1 The exterior electrical outlet by the front door shall have a cover plate 3) 315.2.1 Storage shall be maintained 18" below sprinkler head deflectors 4) 901.6 The spool piece on the riser below the check valve is badly corrided and shall be replaced 5) 605.5 Extention cords shall not be used in place of permanent wiring nor run under doors 6) 315.2.3 Equipment rooms shall not be used for combustable storage 7) 703.2.2 Corridor doors shall not be blocked open 8) 315 (misc. combustable storage) The office area of sherry is in need of housekeeping. The amount of combustables is only adding to the fire load. |