Case: T08FR01162
Case Details
Entered Date:
05/08/2008
Applicant:
TUCSON PLACE PARTNERS LLC
Description:
Full Inspection.
Outstanding Inspections
Case Number: T08FR01162
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/08/2008 | VIOL - FIRE SERVICE FEATURES | JBURGE | Correction Required | TFC 510.1- Identification. Post a permanent, durable and readily visible sign on one of the double doors located in the men's restroom. The sign shall state, "SPRINKLER SYSTEM RISER INSIDE." |
05/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.5- Extension cords. Remoe the two extension cords located in the sales development room. |
05/08/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6- Unapproved conditions. All open spaces in the electrical panels located in the stock room shall be properly covered. |
05/08/2008 | VIOL - FIRE RESIST.RATED CONST | JBURGE | Correction Required | TFC 703.1- Maintenance. Replace the missing ceiling tiles located in the fire alarm control panel room. |
05/08/2008 | VIOL - FIRE PROTECTION SYSTEMS | JBURGE | Correction Required | TFC 901.6- Inspection, testing and maintenance. Repair the sprinkiler system fire department connections. The connections will not swivel properly. |
05/08/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8- Door operations. Remove all locking bar hardware from the egress doors. Locking bar hardware is prohibited on egress doors. |
05/08/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1008.1.8.3- Locks and latches. Post a sign on the inside of the entrance doors that have a double keyed lock. The sign shall state, "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED." |
05/08/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- illumination emergency power. Repair or replace the emergency lighting unit located in the speaker room on the ceiling. |
05/08/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- illumination emergency power. Test all emergency lighting units and exit signs for emergency back-up power. Replace or repair defective units. |
05/08/2008 | VIOL - MEANS OF EGRESS | JBURGE | Correction Required | TFC 1027.5- illumination emergency power. The exit sign and emergency lighting unit located in the north exit corridor shall have emergency back-up power. |
05/08/2008 | VIOL - COMPRESSED GASES | JBURGE | Correction Required | TFC 3003.5.3- Securing compressed gas containers, cylinders and tanks. Secure all compressed gas cylinders located in the stock room. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR01162
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2008 | INSP - FULL | JBURGE | Approved | All noted Tucson Fire Code violations have been corrected. |