Case: T08FR01103
Case Details
Entered Date:
05/05/2008
Applicant:
RIDGETOP TUCSON WG LL
Description:
Full Inspection WALGREENS Building Rep: Robert Hardin Phone # 623-3125
Outstanding Inspections
Case Number: T08FR01103
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2008 | INSP - FULL | JLONGO | Correction Required | Full Inspection completed. Please correct the following Tucson Fire Code Violations. |
05/05/2008 | VIOL - PRECAUTION AGAINST FIRE | JLONGO | Correction Required | 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. ____ Lower storage and maintain ceiling and Sprinkler head clearance according to the fire code. 315.2 Storage in buildings Storage of combustible materials shall be order _____ Clean, remove, or place all cluttered combustibles in a orderly fashion. 315.2.3 Equipment rooms Combustible materials shall not be stored in boiler rooms, mechanical rooms, or electrical equipment rooms. _____ Remove all clutter and combustable material from your electrical (camera) room. |
05/05/2008 | VIOL - FIRE SERVICE FEATURES | JLONGO | Correction Required | 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash, storage and other materials or objects shall not be placed or kept near fire hydrants, fire department inlet connections or fire protection system control valves in a manner that would prevent such equipment or fire hydrants from being immediately discernible. The fire department shall not be deterred or hindered from gaining immediate access to fire protection equipment or fire hydrants. _____ Maintain proper working clearance around the sprinkler riser. |
05/05/2008 | VIOL - BUILDING SVCS & SYSTEMS | JLONGO | Correction Required | 605.3 Working space and clearance A working space of not less than 30 inches in width, 36 inches in depth, and 78 inches in height shall be provided in front of electrical service equipment. Where the service equipment is wider than 30 inches, working space shall be no less than the width of the equipment. No storage of any kind shall be located within the designated working space. _____ Remove all obstruction around electrical panels to maintain the required working space need to meet code standards |
05/05/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLONGO | Correction Required | 906.6 Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. ______ Remove all object that obstruct the view of all portable fire exstinguishers or move the exstinguishers into a location where it can be easily identified. 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. _____ Please hang all portable fire exstinguishers on thier required brackets and secure them according to code. |
05/05/2008 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists… -- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: -- 2.1. The locking device is readily distinguishable as locked, -- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, -- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____ Place the wording "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" above main entrance door 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed… Each door in a means of egress from a Group A or E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. * The placement of any other hardware on a panic hardware door, shall not be allowed and should be removed. 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code _____ Fix the two exit signs located main lobby of the store as they do not have back up power. 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: all Emergency lighting shall be functional and properly maintained in conjunction with IFC section 1027. _____ Fix the damaged emergency lighting located in the rear storage room. 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. _____ In the storage room, remove all obstructions away from the egress door in order to maintain the proper path of egress. |
05/05/2008 | VIOL - COMPRESSED GASES | JLONGO | Correction Required | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. _____ compressed gas containers must be secured at all times. secure both bottles in the photo area properly. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ______________________ Joseph P. Longo |