Inspection Status: Correction Required
Inspection History: VIOL - PRECAUTION AGAINST FIRE
Case Number - T08FR01103
Inspection Description - VIOL - PRECAUTION AGAINST FIRE
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/05/2008 | VIOL - PRECAUTION AGAINST FIRE | Correction Required | 315.2.1 Ceiling clearance Storage shall be maintained 2 feet or more below the ceiling in non-sprinklered areas of buildings or a minimum of 18 inches below sprinkler head deflectors in sprinklered areas of a building. ____ Lower storage and maintain ceiling and Sprinkler head clearance according to the fire code. 315.2 Storage in buildings Storage of combustible materials shall be order _____ Clean, remove, or place all cluttered combustibles in a orderly fashion. 315.2.3 Equipment rooms Combustible materials shall not be stored in boiler rooms, mechanical rooms, or electrical equipment rooms. _____ Remove all clutter and combustable material from your electrical (camera) room. |