Case: T08FR00893
Case Details
Entered Date:
04/09/2008
Applicant:
WINGED FOOT ASSOCIATES
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR00893
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 13
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/09/2008 | VIOL - FIRE SERVICE FEATURES | MWAINWRI | Violation | 2006 IFC 504.2 PLACE A SIGN ON THE OUTSIDE WAREHOUSE DOOR IN 6 INCH LETTERS "THIS DOOR BLOCKED" IN CONTRASTING COLOR |
04/09/2008 | VIOL - FIRE SERVICE FEATURES | MWAINWRI | Violation | 2006 IFC 505.1 INSTALL ADDRESS NUMBERS ON BUILDING ACCORDING TO PIMA COUNTY ADDRESSING CODE. |
04/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.1 INSTALL PLASTIC BLANKS IN THE ELEC PANELS IN WAREHOUSE AREA AND KEEP A 36 INCH CLEARANCE |
04/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.1 KEEP ELEC PANEL DOOR CLEAR OF OBSTRUCTIONS IN STORAGE OVER FLOW ROOM |
04/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.1 REPLACE THE 2 CORD REELS IN THE MEAT DEPT. THE CORD WIRES ARE FRAYED AND STRETCHED. |
04/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.5 REMOVE EXTENSION CORD BY BREAD CASE |
04/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.5 REMOVE EXTENSION CORD IN MEAT DEPT REMOVE EXT CORD USED FOR THE SM HOBART MACHINCE REMOVE EXT CORD BY SLICER IN DELI AREA |
04/09/2008 | VIOL - BUILDING SVCS & SYSTEMS | MWAINWRI | Violation | 2006 IFC 605.5 REMOVE EXTENSION CORD ON COCA COLA NEON SIGN IN DELI/REST AREA REMOVE EXTENSION CORD IN COFFEE BAR BY SINK |
04/09/2008 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 901.6 RELOCATE FIRE EXTINGUISHER IN THE MARKET WHICH IS BEHIND THE MARLBORO MACHINE |
04/09/2008 | VIOL - FIRE PROTECTION SYSTEMS | MWAINWRI | Violation | 2006 IFC 904.11.6.3 HAVE DUCT CLEANED OVER THE OPEN FLAME CHARBROILER. CLEAN DUCT THE THE ROOF. |
04/09/2008 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1008.1.8 REMOVE DBL KEYED LOCK ON EXIT DOOR IN STORAGE ROOM AND REPLACE WITH A THUMB TURN |
04/09/2008 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1027.5 REPAIR EMERGENCY LIGHTS ON GROCERY SIDE REPAIR EMERGENCY LIGHTS ON DELI SIDE/PRODUCE |
04/09/2008 | VIOL - MEANS OF EGRESS | MWAINWRI | Violation | 2006 IFC 1028.2 UNBLOCK THE WEST EXIT DOOR IN THE RESTAURANT AND REMOVE TABLES IN FRONT OF THE DOOR. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00893
Case Description: INSPECTION
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/23/2008 | INSP - FULL | MWAINWRI | Approved |