Case: T08FR00893

Parcel: 12507172A


Addresses:

2513 E 6TH ST


Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T08FR00893

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
04/09/2008 VIOL - BUILDING SVCS & SYSTEMS Violation 2006 IFC 605.5
REMOVE EXTENSION CORD BY BREAD CASE
04/09/2008 VIOL - BUILDING SVCS & SYSTEMS Violation 2006 IFC 605.1
KEEP ELEC PANEL DOOR CLEAR OF OBSTRUCTIONS IN STORAGE OVER FLOW ROOM
04/09/2008 VIOL - BUILDING SVCS & SYSTEMS Violation 2006 IFC 605.1
REPLACE THE 2 CORD REELS IN THE MEAT DEPT. THE CORD WIRES ARE FRAYED AND STRETCHED.
04/09/2008 VIOL - BUILDING SVCS & SYSTEMS Violation 2006 IFC 605.5
REMOVE EXTENSION CORD IN MEAT DEPT
REMOVE EXT CORD USED FOR THE SM HOBART MACHINCE
REMOVE EXT CORD BY SLICER IN DELI AREA
04/09/2008 VIOL - BUILDING SVCS & SYSTEMS Violation 2006 IFC 605.1
INSTALL PLASTIC BLANKS IN THE ELEC PANELS IN WAREHOUSE AREA AND KEEP A 36 INCH CLEARANCE
04/09/2008 VIOL - BUILDING SVCS & SYSTEMS Violation 2006 IFC 605.5
REMOVE EXTENSION CORD ON COCA COLA NEON SIGN IN DELI/REST AREA
REMOVE EXTENSION CORD IN COFFEE BAR BY SINK