Case: T08FR00841
Case Details
Entered Date:
04/02/2008
Applicant:
TUCSON PLACE PARTNERS LLC
Description:
Full Inspection THE OAK STORE Building Rep: Kriten Kellman Phone # 887-7535 Suite 125
Outstanding Inspections
Case Number: T08FR00841
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/02/2008 | INSP - FULL | JLONGO | Correction Required | Full Inspection Completed. Please correct the following Tucson fire Code Violations. * If you wish to remove the "SOUTH EAST" door as an exit, you must contact DSD at 520-791-5550. |
04/02/2008 | VIOL - FIRE RESIST.RATED CONST | JLONGO | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire _____ Fix ceiling tiles, cover openings. |
04/02/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLONGO | Correction Required | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. -- ---Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. _____ All protable fire extinguishers are to be serviced and tested. |
04/02/2008 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use. ____ Move all objects that block direct access to the south east egress door. Proper access will be maintained at all times. _____ Remove double key lock from south est door and replace with a thumb-turn lock. 1011.5.3 Power source. Exit signs shall be illuminated at all times. To ensure continued illumination for a duration of not less than 90 minutes in case of primary power loss, the sign illumination means shall be connected to an emergency power system provided from storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code _____ fix all emergency exits ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ______________________ Joseph P. Longo |