Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

03/27/2008

Applicant:

KOTZAMBASIS PTOLEMEOS & LOIS

Description:

Full Inspectio C&N Auto Repair Building Rep: Chanh Nguyen Phone # 481-7696

Outstanding Inspections

Case Number: T08FR00802
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
03/27/2008 INSP - FULL JLONGO Correction Required Full Inspection completed. FPI was a direct result of a complaint that the buisness was spray painting vehicals in violation of code requirments. No painting shall be allowed within in the building as it fails the Tucson Fire Code requirements. Also please correct the following Tucson Fire Code Violations.
03/27/2008 VIOL - PRECAUTION AGAINST FIRE JLONGO Correction Required 310.3 "No Smoking" signs. The fire code official is authorized to order the posting of "No Smoking" signs in a conspicuous location in each structure or location in which smoking is prohibited. The content, lettering, size, color and location of required "No Smoking" signs shall be approved. _____ Place "NO SMOKING" signs through out the entire work area
03/27/2008 VIOL - FIRE PROTECTION SYSTEMS JLONGO Correction Required 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. _____ Properly service and mount all portable fire extinguishers
03/27/2008 VIOL - MEANS OF EGRESS JLONGO Correction Required 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. _____ Remove key turn bolt lock from main entrance door 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists… -- 2. In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F, M and S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: -- 2.1. The locking device is readily distinguishable as locked, -- 2.2. A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall be in letters 1 inch (25 mm) high on a contrasting background, -- 2.3. The use of the key-operated locking device is revokable by the fire code official for due cause. _____ Properly label "THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED" above main entrance door
03/27/2008 VIOL - FLAMMABLE FINISHES JLONGO Correction Required In accordance with the International Fire Code chapter 15, you do not met the proper requirements to spray or paint any vehicals within your building. * No painting shall be allowed inside of your buisness and all painting must happen outside.
03/27/2008 VIOL - HAZARDOUS MATERIALS,GEN JLONGO Correction Required 2703.5 Hazard identification signs. Unless otherwise exempted by the fire code official, visible hazard identification signs as specified in NFPA 704 for the specific material contained shall be placed on stationary containers and above-ground tanks and at entrances to locations where hazardous materials are stored, dispensed, used or handled in quantities requiring a permit and at specific entrances and locations designated by the fire code official. _____ Properly label barrel "waste oil" to make it easily distinguishable
03/27/2008 VIOL - FLAMMABLE LIQUIDS JLONGO Correction Required 3404.3.4.4 Liquids for maintenance and operation of equipment. In all occupancies, quantities of flammable and combustible liquids in excess of 10 gallons (38 L) used for maintenance purposes and the operation of equipment shall be stored in liquid storage cabinets in accordance with Section 3404.3.2. Quantities not exceeding 10 gallons (38 L) are allowed to be stored outside of a cabinet when in approved containers located in private garages or other approved locations. _____ Acquire a approved flammable liquids cabinet and store all of your flammable liquids safetly inside ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you.