Case: T08FR00553
Case Details
Entered Date:
02/25/2008
Applicant:
SILVERADO PLAZA I LLC
Description:
General Inspection
Outstanding Inspections
Case Number: T08FR00553
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/25/2008 | INSP - FULL | JBEZEL | Correction Required | The Tucson Fire Department has conducted a fire safety inspection at the above stated business . Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code (with modifications). ___1. PROBLEM: Electrical cord running through ceiling from front window sign. TFC REFERENCE: 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. REQUIRED CORRECTION: Plug sign into outlet or power strip. No electrical cords are to be run through the ceiling or ceiling tile. ___2. PROBLEM: Escutcheon plates missing from sprinkler heads in front, in back and in office. TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. REQUIRED CORRECTION: Have missing escutcheon plates replaced on sprinkler heads. ___3. PROBLEM: Emergency lighting unit above office inoperable. TFC REFERENCE: 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. REQUIRED CORRECTION: Have emergency lighting unit serviced. ___4. PROBLEM: Fire extinguisher in office has out-dated service tag and is not mounted on a bracket. TFC REFERENCE: 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. AND: 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer’s installation instructions. REQUIRED CORRECTION: Have portable fire extinguisher serviced and mounted on a bracket. The Tucson Fire Department is committed to the protection of your property and your life safety. Your help as a business owner and as a citizen is greatly appreciated Property Representative Signature: _________________________. Fire Inspector Signature: _________________________(791-4502). Reinspection Date: ___/___/___ or later. __X_Approved ___Not Approved |