Case: T08FR00517
Case Details
Entered Date:
02/22/2008
Applicant:
CIRCLE PLAZA ASSOCIATES LLC 50% &
Description:
FULL FIRE INSPECTION
Outstanding Inspections
Case Number: T08FR00517
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 5
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2008 | VIOL - FIRE SERVICE FEATURES | JVINCENT | Violation | 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. ____ Provide sign for rear exit door. |
| 02/22/2008 | VIOL - FIRE SERVICE FEATURES | JVINCENT | Violation | 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. ____ Label RISER ROOM. |
| 02/22/2008 | VIOL - BUILDING SVCS & SYSTEMS | JVINCENT | Violation | 605.3.1 Labeling. Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording. ____ Label electrical room. |
| 02/22/2008 | VIOL - FIRE PROTECTION SYSTEMS | JVINCENT | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____ Service and tag extinguisher in electrical room. |
| 02/22/2008 | VIOL - MEANS OF EGRESS | JVINCENT | Violation | 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate... ____ Repair emergency lighting units. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00517
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/11/2008 | INSP - FULL | JVINCENT | Approved | ALL VIOLATIONS CORRECTED. 04/11/2008. |