Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - FIRE SERVICE FEATURES
Case Number - T08FR00517
Inspection Description - VIOL - FIRE SERVICE FEATURES
Inspection Status - Violation
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/22/2008 | VIOL - FIRE SERVICE FEATURES | Violation | 504.2 Maintenance of exterior doors and openings. Exterior doors and their function shall not be eliminated without prior approval. Exterior doors that have been rendered nonfunctional and that retain a functional door exterior appearance shall have a sign affixed to the exterior side of the door with the words THIS DOOR BLOCKED. The sign shall consist of letters having a principal stroke of not less than 0.75 inch (19.1 mm) wide and at least 6 inches (152 mm) high on a contrasting background. ____ Provide sign for rear exit door. |
|
| 02/22/2008 | VIOL - FIRE SERVICE FEATURES | Violation | 510.1 Identification. Fire protection equipment shall be identified in an approved manner. Rooms containing controls for air-conditioning systems, sprinkler risers and valves, or other fire detection, suppression or control elements shall be identified for the use of the fire department. Approved signs required to identify fire protection equipment and equipment location, shall be constructed of durable materials, permanently installed and readily visible. ____ Label RISER ROOM. |