Case: T08FR00516
Case Details
Entered Date:
02/22/2008
Applicant:
N/A
Description:
Full Inspection BlockBuster Videos Building Rep: Bob Lindsey Contact# 520-887-5337
Outstanding Inspections
Case Number: T08FR00516
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/22/2008 | INSP - FULL | JLONGO | Correction Required | C of O was on hand, building type B-2. Please correct the following Tucson Fire Code Violations. |
02/22/2008 | VIOL - FIRE RESIST.RATED CONST | JLONGO | Correction Required | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, firestops, shaft enclosures, partitions, smoke barriers, floors, fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated. Openings made therein for the passage of pipes, electrical conduit, wires, ducts, air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire ____ Place appropriate cover over bath room fan |
02/22/2008 | VIOL - FIRE PROTECTION SYSTEMS | JLONGO | Correction Required | 906.6 Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. ____ Lable the protable fire extingusher behind main check out desk |
02/22/2008 | VIOL - MEANS OF EGRESS | JLONGO | Correction Required | 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises' electrical supply, in the event of power supply failure, an emergency electrical system shall automatically illuminate… The emergency power system shall provide power for a duration of not less than 90 minutes and shall consist of storage batteries, unit equipment or an on-site generator. The installation of the emergency power system shall be in accordance with Section 2702 of the International Building Code. ____ Fix all emergency lighting 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ____ REMOVE key locks on all egress doors, and replace with a thumb turn latch. 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of door leaf width. 2. The maximum unlatching force shall not exceed 15 pounds (67 N). ____ Fix south east exit door 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. ____ Remove thumb-turn lock from sout east exit, even if inoperable 1011.4 Internally illuminated exit signs. Internally illuminated exit signs shall be listed and labeled and shall be installed in accordance with the manufacturer's instructions and Section 2702 of the International Building Code. Exit signs shall be illuminated at all times. ____ Fix all Exit signs according to code Additionally: Keep all means of egrees clear of debris, and maintain all proper egress width. Thank you. ________________________________________________ (Joseph P. Longo, Inspector, Tucson Fire Department) I, ______________________ have received a copy of this inspection report. (Building Representative) ______________________________ (Captain) Full inspection done by Inspector Joseph P. Longo Re-inspection scheduled on or after ___/___/___ Call Inspector Longo at 235-4262 or 791-4502, if you have any further questions. Thank you. Re-inspection passed: ______________________ Joseph P. Longo |