Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/21/2008

Applicant:

KVOA COMMUNICATIONS INC

Description:

Full Inspection.

Outstanding Inspections

Case Number: T08FR00511
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 20
End Date Description Inspector Results Comments
02/21/2008 VIOL - PRECAUTION AGAINST FIRE JBURGE Correction Required TFC 315.2.3- Remove all storage from the electrical/compressor room located outside.
02/21/2008 VIOL - FIRE SERVICE FEATURES JBURGE Correction Required TFC 506.1- Purchase a fire department lock box and provide all necessary keys to gain access into the building.
02/21/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1- Open spaces in the electric panels shall be covered with an electrical blank, located in the studio.
02/21/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1- Open spaces in the electrical panels shall be covered with an electrical blank, located in the FR room.
02/21/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.1- Repair the electrical box located in traffic by Christina's desk.
02/21/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.4- Remove the un-fused multiplug adapter located in the news room by the coffee maker. NOTE: Replace it with a fused power strip.
02/21/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5- Remove all extension cords from the master control room. NOTE: Replace them with a fused power-strip.
02/21/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5- Remove the extension cord located in the break room. NOTE: Replace them with a fused power strip.
02/21/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.5- Remove the extension cord used the humidifier located in the poduction control room. NOTE: Replace it with a fused power strip.
02/21/2008 VIOL - BUILDING SVCS & SYSTEMS JBURGE Correction Required TFC 605.6- Replace all missing electrical outlet covers located in the production control room.
02/21/2008 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1- Replace all ceiling insulation located in storage above traffic.
02/21/2008 VIOL - FIRE RESIST.RATED CONST JBURGE Correction Required TFC 703.1- Replace all missing ceiling tiles located in the server room.
02/21/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1008.1.3.4- Post a sign stating,"PUSH TO EXIT" on or near the manual unlocking device for all exterior gates. The lettering shall be at least 1 inch in height and have a stroke of not less than 1/8 inch on a contrasting background.
02/21/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3- The exit sign located by the rack room shall be illuminated.
02/21/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.3- The exit sign located in the news room located by the edit bays shall be illuminated.
02/21/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.4- The exit sign located by sales shall have emergency back-up power to remain illuminated.
02/21/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.4- The exit sign located in the studio shall have emergency back-up power to remain illuminated.
02/21/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1027.5- Repair the emergency lighting unit located by the stairway for accounting storage.
02/21/2008 VIOL - MEANS OF EGRESS JBURGE Correction Required TFC 1028.8- Remove the double-keyed lock from the panic hardware door located in the news room.
02/21/2008 VIOL - HAZARDOUS MATERIALS,GEN JBURGE Correction Required TFC 2703.8.7- All flamable and combustible liquids shall be stored in an approved flamable liquids cabinet. Reduce quantities and consolidate like materials.

Completed Inspections

Case Status: COMPLETE
Case Number: T08FR00511
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
03/12/2008 INSP - FULL JBURGE Approved All noted Tucson Fire Code violations have been corrected.