Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR00511

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/21/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.4- The exit sign located by sales shall have emergency back-up power to remain illuminated.
02/21/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.4- The exit sign located in the studio shall have emergency back-up power to remain illuminated.
02/21/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1028.8- Remove the double-keyed lock from the panic hardware door located in the news room.
02/21/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.3- The exit sign located in the news room located by the edit bays shall be illuminated.
02/21/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.3- The exit sign located by the rack room shall be illuminated.
02/21/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1.3.4- Post a sign stating,"PUSH TO EXIT" on or near the manual unlocking device for all exterior gates. The lettering shall be at least 1 inch in height and have a stroke of not less than 1/8 inch on a contrasting background.
02/21/2008 VIOL - MEANS OF EGRESS Correction Required TFC 1027.5- Repair the emergency lighting unit located by the stairway for accounting storage.