Case: T08FR00492
Case Details
Entered Date:
02/15/2008
Applicant:
MENLO PARK SHOPPING CENTER COMPANY
Description:
Called out by Medic 1 for electrical hazards.
Outstanding Inspections
Case Number: T08FR00492
Case Status: COMPLETE
Case Description: COMPLAINT (COMMERCIAL)
Total Outstanding Inspections - 4
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/15/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.1 Abatement of electrical hazards. Repair the leaks in the roof so water cannot flow into the electrical service equipment. |
02/15/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.1- Remove all moisture from the electrical service panels and have all electrical systems checked by an electrical contractor. |
02/15/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.3 No storage of any materials shall be located within 36 inches of electrical service equipment. |
02/15/2008 | VIOL - BUILDING SVCS & SYSTEMS | JBURGE | Correction Required | TFC 605.6- Provide blanks for all open spaces in the electrical panels. |
Completed Inspections
Case Status: COMPLETE
Case Number: T08FR00492
Case Description: COMPLAINT (COMMERCIAL)
Total Completed Inspections - 1
End Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
02/29/2008 | INSP - LIFE SAFETY | JBURGE | Approved | All noted Tucson Fire Code violations were corrected. |